CIRCUIT-INTEGRATION MODULE PROVIDES A COMMUNICATION LINK BETWEEN A VESDANET NETWORK AND A FIRE ALARM CONTROL PANEL VIA THE VHX-1420-HFS
The Signaling Line Circuit-Integration Module (SLC-IM) provides a communication link between a VESDAnet network and a Fire Alarm Control Panel (FACP) SLC loop via the High Level Interface (HLI) VHX-1420-HFS. It allows mapping of alarms and faults from VESDA detectors onto FACP monitor module addresses. The SLC-IM translates VESDAnet protocol to SLC protocol, enabling VESDA detector events on the VESDAnet to be annunciated by an FACP.